Lightning Protection Products 
		  
	  
       
	  ZoneDefender² Series_ZD16800* 、ZD16801*、ZD16809+、ZD16820、ZD16821、ZD14612、ZD14624、ZD14648、ZD14712、ZD14724、ZD14748

Product No:Pro200965113315
Product Model:ZD16800* 、ZD16801*、ZD16809+、ZD16820、ZD16821、ZD14612、
UpdateTime:
Views:1396

Details:

ZoneDefender2
80kA power surge protection for small distribution panels,tower lights, equipment cabinets and confined spaces
 AC or DC application
 AC or DC application Straightforward and simple installation --wall or fl ush mounting
 Straightforward and simple installation --wall or fl ush mounting LED status indication via solid state diagnostics plus remote indication contacts
 LED status indication via solid state diagnostics plus remote indication contacts Thermal and short circuit fusing
 Thermal and short circuit fusing UL 1449 Listed
 UL 1449 Listed 10 year product warranty
 10 year product warrantySpecifi cation
All fi gures typical at 77°F (25°C) unless otherwise stated
Maximum surge current
80kA (8/20μs)*
*except ZoneDefender2 DC versions.
See specifi cations table for details.
Lines protected AC
L-N, L-G/E, L-L, N-G/E
Lines protected DC
V+, VDuty
cycle perormance (8/20μs)
80,000A 1 impulse
10,000A >4,000 impulses
100A infi nite
Long duration current pulse (10/1,000μs) capability
3,600A (tested)
Response time
<5ns
Ambient temperature limits
–40°F to +185°F (–40°C to +85°C) — working
Humidity
95% RH (non-condensing)
Enclosure
NEMA 1, 2, 3, 3R, 4, 4X, 12 and 13 (IP66)
Terminals
12 AWG (3mm2)
Mounting
Surface mount by four 0.17” (4mm) diameter holes
Optional fl ush mount (add suffi x “F” to Model number)
Remote contacts
C, NO, NC rated 60W DC or 120VA AC, 3A max.
Indication
Green LED on Protection present
Green LED off Internal failure or no power
Red LED on Internal failure
Weight
2.1 lbs (0.94Kg)
Dimensions
4.0” x 4.0” x 2.4”
(102mm x 102mm x 61mm)
AIC Rating
Suitable for use on a circuit capable of delivering not
more tha 100,000 rms symmetrical Amperes, 240V
maximum
EMC compliance
BS EN 60950: 1992
BS EN 61000-6-2: 1999
| Working voltage (V) | UL 1449 Listing (V) | Limiting voltage | Max.continuous operating voltage (Vac) | Phase types | ||
| @ 3kA+(V) | @ 10kA (In)+(V) | |||||
| AC versions | ||||||
| ZD16800* | 120 | 400 | 430 | 690 | 140 | Single phase 2-wire US | 
| ZD16801* | 120/240 | 400 | 430 | 690 | 140 | Split phase 3-wire US | 
| ZD16809+ | 240 | 800 | 925 | 1200 | 320 | Single phase 2-wire EU | 
| ZD16820 | 120 | 400/800 | 430/925 | 690/1200 | 140/320 | Single phase 2-wire TT | 
| ZD16821 DC versions | 120/240 | 400/800 | 430/925 | 690/1200 | 140/320 Max. surge current | Single phase 3-wire TT | 
| ZD14612 | 12V DC | N/A | 120 | 292 | 15kA | ----- | 
| ZD14624 | 24V DC | N/A | 140 | 340 | 36kA | ----- | 
| ZD14648 | 48V DC | N/A | 280 | 504 | 53kA | ----- | 
| ZD14712 | 12V DC | N/A | 120 | 292 | 15kA | EMI filter | 
| ZD14724 | 24V DC | N/A | 140 | 340 | 36kA | EMI filter | 
| ZD14748 | 48V DC | N/A | 280 | 504 | 53kA | EMI filter | 