Lightning Protection Products
FP32
Product No:Pro200965104434
Product Model:FP32
UpdateTime:
Views:1072
Details:
FP32
Din rail mounting, 20kA surge protection for Fieldbus systems
DIN rail mounting for easy installation and automatic earthing (grounding)
20kA maximum surge current per line
Plug connectors for quick and easy connection or rewiring
Meets the requirements of IEC 61158-2:2000 for FOUNDATION FIELDBUS
10 year product warranty
Specifi cation
All fi gures typical at 77°F (25°C) unless otherwise stated
Maximum surge current
20kA (8/20μs waveform) per line
Leakage current
<1mA @ working voltage
Working voltage
±32Vdc
Maximum continuous operating voltage
±36V peak normal mode
±225V peak common mode
Limting voltage
62V @ 3kA 8/20μs
Line resistance
0.5Ω per line
Capacitance
Line — Line — 40pF
Line — Earth (Ground) — 80pF
Attenuation
-1dB — 7kHz-7.5mHz
Ambient temperature limits
-40°F — +158°F (-40°C — +70°C) — working
-40°F — +176°F (-40°C — +80°C) — storage
Humidity
5% to 95% RH (non-condensing)
Electrical connections
Plug/header screw terminal strip
Weight
5.0 oz (140g approx)
Dimensions
See fi gure 1
EMC compliance
BS EN 60950:1992
BS EN 61000-6-2:1999
BS EN 61010-1:1993
Electrical Safety
ATEX II 3 G
DOC #MTL02ATEX0032X
Model | FP32 | |
Nominal voltage | Un | 32V |
Rated voltage (MCOV) | Uc | 36V |
Nominal current | In | 1.6A |
Nominal discharge current (8/20μs) | isn | 3kA |
Max discharge current (8/20μs) | Imax | 20kA |
Lightning impulse current (10/350μs) | Iimp | 2.5kA |
Residual voltage @ isn | Up | 62V |
Voltage protection level @ 1kV/μs | Up | <45V |
Bandwidth | fG | 73MHz |
Capitance | C | 40pF |
Series resistance | R | 0.5 |
Operating Temperature Range | -40°C to +70°C | |
Category tested | A2, B2, C1, C2, C3, D1 | |
Overstressed fault mode in=3kA | 22kA | |
Impulse durability (8/20μs) | 10kA | |
Degree of protection | IP20 | |
AC durability | 1Arms, 5T | |
Service conditions | 80kPa - 160kPa 5% - 95% RH |
Download:
FP32.pdf