TP24/7
Safeguards 4 wire process transmitters against induced surges and transients from field cabling

 Specifi cally designed for Multivariable Transmitters and Level Transmitters
 Four wires protected, one pair at 12V to 24V and one pair at 7V (e.g. RS485)
 Easy and direct mounting - simply screws into spare conduit entry
 Intrinsically safe and fl ameproof to CENELEC standards
 FM for US and Canada and ATEX approved

Specifi cation

All fi gures typical at 77°F (25°C) unless otherwise stated
Maximum surge current
10kA peak current (8/20μs waveform)
Leakage current
Less than 10μA at maximum working
voltage
Working voltage
12V to 24V dc power
7V dc maximum RS485 communications
Bandwidth
1MHz
Resistance
No resistance introduced into loop
Ambient temperature limits
-40°C to +60°C (working)
-40°C to +85°C (storage)
Humidity
5% to 95% RH (non-condensing)
Electrical connections
4 fl ying leads
Wire size 32/0.2 (1.0mm2, 18 AWG)
Lead length 250mm (minimum)
Casing
ANSI 316 stainless steel hexagonal barstock,
male thread
Threads
TP24/7-N 1/2” NPT
TP24/7-I 20mm ISO (M20 x 1.5)
TP24/7-G G 1/2” (BSP 1/2 inch)
Weight
175g (6.2 oz)
Dimensions
See fi gure 1
EMC compliance
To Generic Immunity Standards EN50082,
part 2 for industrial environments
Electrical safety
EEx ia IIC T4, Ceq=O, Leq=0; the unit can be connected without further certifi cation into any intrinsically safe loop with open circuit voltage <60V and input power<1.2W.
EEx d IIC T4; the unit is apparatus-approved to fl ame proof (explosionproof) standards, and can be fi tted into a similarly approved housing.


Model TP24/7
Nominal voltage Un 24V/7V
Rated voltage (MCOV) Uc 34V/7V
Nominal current In n/a
Nominal discharge current (8/20μs) isn 3kA
Max discharge current (8/20μs) Imax 10kA
Lightning impulse current (10/350μs) Iimp 2.5kA
Residual voltage @ isn Up 43V/19V
Voltage protection level @ 1kV/μs Up <36V/<12V
Bandwidth fG 1MHz
Capacitance C 100pF
Series resistance R n/a
Operating Temperature Range -40°C to +85°C
Category tested A2, B2, C1, C2, C3, D1
Overstressed fault mode in=3kA 12kA
Impulse durability (8/20μs) 10kA
Degree of protection IP66
AC durability 1Arms, 5T
Service conditions 80kPa - 160kPa 5% - 95% RH