Lightning Protection Products

DEHNguard M TT 2P (FM)

Product No:Pro200964104133
Product Model:DEHNguard M TT 2P (FM)
UpdateTime:
Views:1573

Details:

DEHNguard M TT 2P (FM)
DEHNguard M TT 2P ... (FM) Dimension drawing DG M TT 2P ... FM Basic circuit diagram DG M TT 2P ... FM
DG M TT 2P ... (FM): Modular surge arrester for use in single-phase 230 V TT and TN systems (1+1 circuit)
DG M TT 2P 275 | DG M TT 2P 275 FM | |
Type of SPD according to EN 61643-11 | Type 2 | Type 2 |
SPD according to IEC 61643-1 | Class II | Class II |
Nominal a.c. voltage [UN] | 230 V | 230 V |
Max. continuous operating a.c. voltage [L-N] [UC] | 275 V | 275 V |
Max. continuous operating a.c. voltage [N-PE] [UC] | 255 V | 255 V |
Nominal discharge current (8/20 µs) [In] | 20 kA | 20 kA |
Max. discharge current (8/20 µs) [Imax] | 40 kA | 40 kA |
Lightning impulse current (10/350 µs) [N-PE] [Iimp] | 12 kA | 12 kA |
Voltage protection level [L-N] [UP] | ≤ 1.25 kV | ≤ 1.25 kV |
Voltage protection level [L-N] for 5 kA [UP] | ≤ 1 kV | ≤ 1 kV |
Voltage protection level [N-PE] [UP] | ≤ 1.5 kV | ≤ 1.5 kV |
Follow current extinguishing capability [N-PE] [Ifi] | 100 Arms | 100 Arms |
Response time [L-N] [tA] | ≤ 25 ns | ≤ 25 ns |
Response time [N-PE] [tA] | ≤ 100 ns | ≤ 100 ns |
Max. mains-side overcurrent protection | 125 A gL/gG | 125 A gL/gG |
Short circuit withstand capability for max. mains-side overcurrent protection | 50 kArms | 50 kArms |
Temporary overvoltage (TOV) [L-N] [UT] | 335 V / 5 sec. | 335 V / 5 sec. |
Temporary overvoltage (TOV) [N-PE] [UT] | 1200 V / 200 ms | 1200 V / 200 ms |
Operating temperature range [TU] | -40°C...+80°C | -40°C...+80°C |
Operating state/fault indication | green / red | green / red |
Cross-sectional area (min.) | 1.5 mm2 solid/flexible | 1.5 mm2 solid/flexible |
Cross-sectional area (max.) | 35 mm2 stranded/25 mm2 flexible | 35 mm2 stranded/25 mm2 flexible |
For mounting on | 35 mm DIN rail acc. to EN 60715 | 35 mm DIN rail acc. to EN 60715 |
Enclosure material | red thermoplastic, UL 94 V-0 | red thermoplastic, UL 94 V-0 |
Degree of protection | IP 20 | IP 20 |
Dimension | 2 mods., DIN 4 | 2 mods., DIN 4 |
Approvals, Certifications | KEMA, VDE, UL, VdS | KEMA, VDE, UL, VdS |
Type of remote signalling contact | -- | changeover contact |
Switching capacity a.c. | -- | 250 V/0.5 A |
Switching capacity d.c. | -- | 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A |
Cross-sectional area for remote signalling terminals | -- | max. 1.5 mm2 solid/flexible |
1 pcs. | 1 pcs. | |
ordering information | ||
Type | DG M TT 2P 275 | DG M TT 2P 275 FM |
Part No. | 952 110 | 952 115 |
Packing unit | 1 pc(s) |