Lightning Protection Products

DEHNguard TT H LI


Product No:Pro20096410926
Product Model:DEHNguard TT H LI
UpdateTime:
Views:1144

Details


DEHNguard TT H LI

                         
DEHNguard TT H LI                       Dimension drawing DG TT H230 400 LI     Basic circuit diagram DG TT H230 400 LI 

DG TT H LI: Multipole surge arrester with Pro-Active Thermo Control SPD monitoring device with 3-stage visual indicator for use in TT and TN-S systems (3+1 circuit)

  DG TT H230 400 LI  DG TT H230 400 LI385 
SPD according to EN 61643-11 Type 2   Type 2  
SPD according to IEC 61643-1 Class II   Class II  
Nominal a.c. voltage 230/400 V  230/400 V 
Max. continuous operating a.c. voltage [L-N] 275 V  385 V 
Max. continuous operating a.c. voltage [N-PE] 255 V  255 V 
Nominal discharge current (8/20 µs)     [In] 20 kA  20 kA 
Max. discharge current (8/20 µs)     [Imax] 65 kA  65 kA 
Max. discharge current (8/20 µs) [L-N]     [Imax] 65 kA  65 kA 
Max. discharge current (8/20 µs) [N-PE] 65 kA  65 kA 
Lightning impulse current (10/350 µs) [N-PE] 12 kA  12 kA 
Voltage protection level [L-N] ≤ 1.25 kV  ≤ 1.75 kV 
Voltage protection level [L-N] for 5 kA ≤ 1 kV  ≤ 1.35 kV 
Voltage protection level [N-PE] ≤ 1.5 kV  ≤ 1.5 kV 
Follow current extinguishing capability [N-PE] 100 Arms  100 Arms 
Response time [L-N] ≤ 25 ns  ≤ 25 ns 
Response time [N-PE] ≤ 100 ns  ≤ 100 ns 
Max. mains-side overcurrent protection 160 A gL/gG  160 A gL/gG 
Short circuit withstand capability for max. mains-side overcurrent protection 20 kArms  20 kArms 
Temporary overvoltage (TOV) [L-N] 335 V / 5 sec.  --  
Temporary overvoltage (TOV) [N-PE] 1200 V / 200 ms  --  
Operating temperature range -40°C...+55°C   -40°C...+55°C  
Cross-sectional area (min.) 1.5 mm2 solid/flexible   1.5 mm2 solid/flexible  
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible   35 mm2 stranded/25 mm2 flexible  
For mounting on 35 mm DIN rail acc. to EN 60715   35 mm DIN rail acc. to EN 60715  
Enclosure material red thermoplastic, UL 94 V-0   red thermoplastic, UL 94 V-0  
Degree of protection IP 20   IP 20  
Dimension 4 mods., DIN 4  4 mods., DIN 4 
Approvals, Certifications KEMA   KEMA  
Type of remote signalling contact --   changeover contact  
Type of remote signalling contact --   changeover contact  
Switching capacity a.c. 250 V/0.5 A   250 V/0.5 A  
Switching capacity d.c. 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A   250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A  
Cross-sectional area for remote signalling terminals max. 1.5 mm2 solid/flexible   max. 1.5 mm2 solid/flexible  
Indication of disconnector green-yellow-red   green-yellow-red  
PU 1 pcs.  1 pcs. 
ordering information
Type DG TT H230 400 LI  DG TT H230 400 LI385 
Part No. 950 150 950 151
Packing unit 1 pc(s)