Lightning Protection Products

DEHNguard TT H LI

Product No:Pro20096410926
Product Model:DEHNguard TT H LI
UpdateTime:
Views:1144

Details:

DEHNguard TT H LI
DEHNguard TT H LI Dimension drawing DG TT H230 400 LI Basic circuit diagram DG TT H230 400 LI
DG TT H LI: Multipole surge arrester with Pro-Active Thermo Control SPD monitoring device with 3-stage visual indicator for use in TT and TN-S systems (3+1 circuit)
DG TT H230 400 LI | DG TT H230 400 LI385 | |
SPD according to EN 61643-11 | Type 2 | Type 2 |
SPD according to IEC 61643-1 | Class II | Class II |
Nominal a.c. voltage | 230/400 V | 230/400 V |
Max. continuous operating a.c. voltage [L-N] | 275 V | 385 V |
Max. continuous operating a.c. voltage [N-PE] | 255 V | 255 V |
Nominal discharge current (8/20 µs) [In] | 20 kA | 20 kA |
Max. discharge current (8/20 µs) [Imax] | 65 kA | 65 kA |
Max. discharge current (8/20 µs) [L-N] [Imax] | 65 kA | 65 kA |
Max. discharge current (8/20 µs) [N-PE] | 65 kA | 65 kA |
Lightning impulse current (10/350 µs) [N-PE] | 12 kA | 12 kA |
Voltage protection level [L-N] | ≤ 1.25 kV | ≤ 1.75 kV |
Voltage protection level [L-N] for 5 kA | ≤ 1 kV | ≤ 1.35 kV |
Voltage protection level [N-PE] | ≤ 1.5 kV | ≤ 1.5 kV |
Follow current extinguishing capability [N-PE] | 100 Arms | 100 Arms |
Response time [L-N] | ≤ 25 ns | ≤ 25 ns |
Response time [N-PE] | ≤ 100 ns | ≤ 100 ns |
Max. mains-side overcurrent protection | 160 A gL/gG | 160 A gL/gG |
Short circuit withstand capability for max. mains-side overcurrent protection | 20 kArms | 20 kArms |
Temporary overvoltage (TOV) [L-N] | 335 V / 5 sec. | -- |
Temporary overvoltage (TOV) [N-PE] | 1200 V / 200 ms | -- |
Operating temperature range | -40°C...+55°C | -40°C...+55°C |
Cross-sectional area (min.) | 1.5 mm2 solid/flexible | 1.5 mm2 solid/flexible |
Cross-sectional area (max.) | 35 mm2 stranded/25 mm2 flexible | 35 mm2 stranded/25 mm2 flexible |
For mounting on | 35 mm DIN rail acc. to EN 60715 | 35 mm DIN rail acc. to EN 60715 |
Enclosure material | red thermoplastic, UL 94 V-0 | red thermoplastic, UL 94 V-0 |
Degree of protection | IP 20 | IP 20 |
Dimension | 4 mods., DIN 4 | 4 mods., DIN 4 |
Approvals, Certifications | KEMA | KEMA |
Type of remote signalling contact | -- | changeover contact |
Type of remote signalling contact | -- | changeover contact |
Switching capacity a.c. | 250 V/0.5 A | 250 V/0.5 A |
Switching capacity d.c. | 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A | 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid/flexible | max. 1.5 mm2 solid/flexible |
Indication of disconnector | green-yellow-red | green-yellow-red |
PU | 1 pcs. | 1 pcs. |
ordering information | ||
Type | DG TT H230 400 LI | DG TT H230 400 LI385 |
Part No. | 950 150 | 950 151 |
Packing unit | 1 pc(s) |