DEHNguard PV ... SCP FM

Product No:Pro20096494823
Product Model:DEHNguard PV ... SCP FM
UpdateTime:
Views:1471

Details:

DEHNguard PV ... SCP FM
DEHNguard PV ... SCP FM Dimension drawing DG PV ... SCP FM Basic circuit diagram DG PV ... SCP FM
DG PV ... SCP FM: Single-pole surge arrester, with combined disconnection and short-circuiting device for use in photovoltaic generator circuits; with floating remote signalling contact
DG PV 500 SCP FM
DG PV 700 SCP FM
DG PV 1200 SCP FM
SPD classification according to EN 61643-11
Type 2
Type 2
Type 2
SPD classification according to IEC 61643-1
Class II
Class II
Class II
PV voltage of earth-free PV systems (2 x DG PV ...) [UPV max]
≤ 1000 V
≤ 1400 V
≤ 1400 V
PV voltage of functionally earthed PV systems (thin film) [UPV max]
≤ 500 V
≤ 700 V
≤ 1200 V
Max. continuous operating d.c. voltage [UC]
500 V
700 V
1200 V
Nominal discharge current (8/20 µs) [In]
20 kA
15 kA
15 kA
Max. discharge current (8/20 µs) [Imax]
30 kA
30 kA
30 kA
Voltage protection level for In [UP]
≤ 2 kV
≤ 2.5 kV
≤ 4.2 kV
Voltage protection level for 5 kA [UP]
≤ 1.7 kV
≤ 2 kV
≤ 3.5 kV
Response time [tA]
≤ 25 ns
≤ 25 ns
≤ 25 ns
Permanent short-circuit withstand capability [IK]
80 A d.c.
80 A d.c.
80 A d.c.
Reverse current withstand capability [Ipmax]
50 kA / 5 ms
50 kA / 5 ms
50 kA / 5 ms
Max. protection of main d.c. line at the inverter
315 A gR
315 A gR
315 A gR
Operating temperature range [TU]
-40°C...+65°C
-40°C...+65°C
-40°C...+65°C
Operating state/fault indication
green / red
green / red
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
1.5 mm2 solid/flexible
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc
35 mm DIN rail acc
35 mm DIN rail acc
Enclosure material
red thermoplastic, UL 94 V-0
red thermoplastic, UL 94 V-0
red thermoplastic, UL 94 V-0
Degree of protection
IP 20
IP 20
IP 20
Dimension
2 mods., DIN 4
2 mods., DIN 4
2 mods., DIN 4
Type of remote signalling contact
changeover contact
changeover contact
changeover contact
Switching capacity a.c.
250 V/0.5 A
250 V/0.5 A
250 V/0.5 A
Switching capacity d.c.
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals
max. 1.5 mm2 solid/flexible
max. 1.5 mm2 solid/flexible
max. 1.5 mm2 solid/flexible
1 pcs.
1 pcs.
1 pcs.
ordering information
Type
DG PV 500 SCP FM
DG PV 700 SCP FM
DG PV 1200 SCP FM
Part No.
950 505 new!
950 506 new!
950 507 new!
Packing unit
1 pc(s)