Lightning Protection Products

DEHNguard Y PV (FM)


Product No:Pro20096493834
Product Model:DEHNguard Y PV (FM)
UpdateTime:
Views:1156

Details


DEHNguard Y PV (FM)

                    
DEHNguard Y PV (FM)        Dimension drawing DG Y PV 1000 (FM)    Basic circuit diagram DG Y PV 1000 (FM)

DG Y PV 1000 ...: Complete circuit for use in photovoltaic installations with UPV max ≤ 1000 V d.c.

  DG Y PV 1000  DG Y PV 1000 FM 
SPD classification according to EN 61643-11 Type 2   Type 2  
SPD classification according to IEC 61643-1 Class II   Class II  
PV voltage acc. to IEC 60364-7-712     [UPV max] ≤ 1000 V  ≤ 1000 V 
Max. continuous operating d.c. voltage [(L+/L-) --> PE]     [Uc] 500 V  500 V 
Nominal discharge current (8/20 µs)     [In] 20 kA  20 kA 
Max. discharge current (8/20 µs)     [Imax] 40 kA  40 kA 
Voltage protection level     [UP] ≤ 4 kV  ≤ 4 kV 
Voltage protection level for 5 kA     [UP] ≤ 3.5 kV  ≤ 3.5 kV 
Response time     [tA] ≤ 25 ns  ≤ 25 ns 
Operating temperature range     [TU] -40°C...+80°C   -40°C...+80°C  
Operating state/fault indication green / red   green / red  
Cross-sectional area (min.) 1.5 mm2 solid/flexible   1.5 mm2 solid/flexible  
Cross-sectional area (max.) 35 mm2 stranded/25 mm2 flexible   35 mm2 stranded/25 mm2 flexible  
For mounting on 35 mm DIN rail acc. to EN 60715   35 mm DIN rail acc. to EN 60715  
Enclosure material thermoplastic, red, UL 94 V-0   thermoplastic, red, UL 94 V-0  
Degree of protection IP 20   IP 20  
Dimension 3 mods., DIN 4  3 mods., DIN 4 
Type of remote signalling contact --   changeover contact  
Switching capacity a.c. --   250 V/0.1 A  
Switching capacity d.c. --   250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A  
Cross-sectional area for remote signalling terminals --   max. 1.5 mm2 solid/flexible  
PU 1 pcs.  1 pcs. 
ordering information
Type DG Y PV 1000  DG Y PV 1000 FM 
Part No. 900 517 900 547
Packing unit 1 pc(s)