Lightning Protection Products

EATON innovative technology U.S._PTE/PTX Series Surge Protection Device_PTX400/PTE400 PTX400-3Y201 PTE400-3Y201 PTX400-3Y201-D/SD PTE400-3Y201-D/SD

Product No:Pro2009427133410
Product Model:PTX400/PTE400 PTX400-3Y201 PTE400-3Y201 PTX400-3Y201-D/SD
UpdateTime:2010.06.03
Views:1952



Summary of technical parameters
Pass the peak flow capacity: Each phase 400KA, each model 200KA
ANSI / IEEE C62.41 installation location: B and C
Applications: high-surge level of activity zones, industrial applications, including large-capacity into line counters, high-capacity distribution of electrical cabinets and a single large load
Warranty: 20 years
Product ID: UL1449 2nd edition, cUL, UL1283
Quality manufacturers: ISO9001: 1994 quality management certificate BSI FM 30833
Mechanical performance parameters
Shell: spray-painted steel structure, all-weather; protection level NEMA4 (IP66)
Fixed: built-wear and multi-point lead pipe fixed angle
Connect: # 14-1/0 (2.5-50mm2) multi-strand wire
Weight: about 14.5 kilograms (32 pounds)
Operating temperature:-400F (-400C) - +1850 F (+850 C)
Electrical performance parameters
Protected Mode: All mode, (three-phase Y-10 model) LN, LL (differential mode), LG, NG (common mode)
The frequency of input power: PTX :47-420 Hz; PTE and-SD :47-64 Hz
Response time: PTX £ 1 nanosecond, PTE <1 nanosecond
Capacitance: PTE: for each mode of <10 μF
Diagnostic instructions: LED instructions, each of the normal green, Remote Alarm Interface (C-type dry-type normally open normally closed contact)
Short-circuit current protection: 200 kAIC the RK5 fuse 100 amps (the factory does not provide)
Maximum EMI / RFI attenuation-Mil-std-220
1 kHz | 10 kHz | 100 kHz | 1 MHz | 10MHz | Maximum attenuation frequency |
3 dB | 21 dB | 40 dB | 22 dB | 6 dB | 40 dB @ 108kHz |
Options
Dynamic Tracking Network (ATN ): PTE
The voice of alarm, surge counter and Phase Monitor (SMARTTM )::(- SD suffix)
NEMA Type 4X stainless steel enclosure: (-SS suffix) (prior notice to the factory, there are at least the number of requirements)
Built-in fuse: (-L suffix) (up-to-date drawings at Division I)
Built-melting filament switch: (-D suffix) (up-to-date drawings at Division I)
ARM-3 Remote Alarm Module
Download: