Lightning Protection Products

EATON innovative technology U.S. _PTE/PTX Series Surge Protection Device_PTX048/PTE048 PTX048-3Y201 PTE048-3Y201 PTX048-3Y201-D/SD PTE048-3Y201-D/SD

Product No:Pro200942713447
Product Model:PTX048/PTE048 PTX048-3Y201 PTE048-3Y201 PTX048-3Y201-D/SD
UpdateTime:2010.06.03
Views:2290


Pass the peak flow capacity: Each phase 48KA, each model 24KA ANSI / IEEE C62.41 placement: A and B
Applications: surge in the level of activity to lower areas, sensitive / important electrical loads including the allocation of cabinet, counter and important user load distribution centers
Warranty: 20 years
Product ID: UL1449 2nd edition, cUL, UL1283
Quality manufacturers: ISO9001: 1994 quality management certificate BSI FM 30833
Mechanical performance parameters
Shell: spray-painted steel structure, all-weather; protection rating NEMA 4 (IP66)
Fixed: built-wear and multi-point lead pipe fixed angle
Connect: # 10 AWG (6 mm2) multi-strand wire
Weight: PTX: about 3 kilograms (7 pounds), PTE: about 5.5 kg (12 lbs)
Operating temperature:-400C - 650C
Electrical performance parameters
Protected Mode: All mode (three-phase Y-10 model): LN, LL (differential mode), LG, NG (common mode)
The frequency of input power: PTX :47-420 Hz; PTE and-SD :47-64 Hz
Response time: PTX £ 1 nanosecond, PTE <1 nanosecond
Capacitance: PTE: for each mode of <10 μF
Diagnosis of instructions: instructions for each LED with normal lights. Remote alarm interface (C-type dry-type normally open normally closed contact)
Short-circuit current protection: 200 kAIC the 30 amps fuse R-class (the factory does not provide)
Maximum EMI / RFI attenuation-Mil-std-220
1 kHz | 10 kHz | 100 kHz | 1 MHz | 10MHz | Maximum attenuation frequency |
3 dB | 20 dB | 40 dB | 23 dB | 7 dB | 40 dB @115 kHz |
Options
Dynamic Tracking Network (ATN ): PTE
The voice of alarm, surge counter and Phase Monitor (SMARTTM )::(- SD suffix)
NEMA Type 4X stainless steel enclosure: (-SS suffix) (prior notice to the factory, there are at least the number of requirements)
Built-in fuse: (-L suffix) (up-to-date drawings at Division I)
Built-melting filament switch: (-D suffix) (up-to-date drawings at Division I)
ARM-3 Remote Alarm Module
Download: