Lightning Protection Products

British MTL Surge Protector_Data and Signal Protection_TP48、TP48/3、TP48/4


Product No:Pro200942794211
Product Model:TP48,TP48/3,TP48/4,TP48-N-NDI,TP48-I-NDI,TP48-G-NDI,TP48-N
UpdateTime:
Views:2311

Details:


The TP48 surge protection device safeguards field-mounted process transmitters where it matters, right at the unit. After a simple installation (the TP48 screws into an unused conduit entry, with no additional modification), it provides high-level protection against surges and transients whilst normal operation remains unaffected. The TP48 resets itself automatically after each operation. The TP48 is available with screw threads to suit different transmitters, with explosion proof and intrinsically safe options for hazardous areas. Working voltage is 48V dc maximum with impulse ratings of 10kA peak current and 10kV peak voltage.

  • Easy and direct mounting - simply screws into spare conduit entry
  • Intrinsically safe and flameproof (explosion proof) approved versions
  • Range of thread types available
  • Fieldbus compatible
  • Available in 2, 3 & 4 wire versions
  • 10 Year No Fuss Warranty

Specifi cation
All fi gures typical at 77°F (25°C) unless otherwise stated
Maximum surge current
10kA peak current (8/20μs waveform)
Leakage current
Less than 10μA at maximum working voltage
Working voltage
48V dc maximum
Bandwidth
1MHz
Resistance
No resistance introduced into loop
Ambient temperature limits
-40°C to +85°C (-40°F to +185°F) (working)
-40°C to +85°C (-40°F to +185°F) (storage)
Humidity
5% to 95% RH (non-condensing)
Electrical connections
TP48
3 fl ying leads (line1, line 2 & earth)
TP48 3 Wire
4 fl ying leads (+ve, -ve, signal & earth)
TP48 4 Wire
5 fl ying leads (+ve, -ve, signal +ve, signal -ve, earth)
Wire size 32/0.2 (1.0mm2, 18 AWG)
Lead length 250mm (minimum)
Casing
ANSI 316 stainless steel hexagonal barstock, male
thread
Threads
TP48-3-N & TP48-4-N 1/2” NPT
TP48-3-I & TP48-4-1 20mm ISO )M20 x 1.5)
TP48-3-G & TP48-4-G G 1/2” (BSP 1/2”)
Weight
175g (6.2oz)
Dimensions
See fi gure 1
EMC compliance
To Generic Immunity Standards EN50082, part 2 for
industrial environments
Electrical safety
EEx ia IIC T4, Ceq=O, Leq=0; the unit can be connected
without further certifi cation into any intrinsically
safe loop with open circuit voltage <60V and input
power <1.2W.
EEx d IIC T4; the unit is apparatus-approved to fl ame
proof (explosionproof) standards, and can be fi tted
into a similarly approved housing.





Download:


  TP48.pdf