FURSE_Lightning signal devices ESP_ESP ThickNet、ESP ThinNet

Product No:Pro2009414235029
Product Model:ESP ThickNet、ESP ThinNet
UpdateTime:2010.06.03
Views:1935

For Thin Ethernet (Cheapernet, IEEE 802.3, 10 base 2) systems use ESP ThinNet.
For Thick Ethernet (IEEE 802.3, 10 base 5) systems use ESP ThickNet.
To protect twisted pair Ethernet (10 or 100 base T) networks with RJ45 connections use ESP Net-100.
Application
Use these protectors on thick and thin Ethernet cables to protect:
computers
transceivers
servers
repeaters
other network equipment
Features and benefits
Let-through voltage below equipment susceptibility levels to ensure effective protection for your equipment.
Protection between all sets of conductors to close all transient paths to equipment (see Ethernet technical note ).
Provides repeated protection - even in lightning intense environments.
Very low reflection coefficient/VSWR ensures that the Lightning Barrier doesn t disrupt network operations.
High bandwidth to prevent the degradation of high frequency signals.
Low in-line resistance to minimise unnecessary reductions in signal strength and maximise signalling distance.
Robust steel housing.
Convenient holes for flat mounting.
Substantial earth stud to enable effective earthing.
Easy installation .
Straightforward and comprehensive installation instructions .
5 year warranty.
Installation
Connect in-line with the Ethernet cable near to where it enters/leaves the building or close to the equipment being protected. This should be close to the system s earth star point (to enable a good connection to earth). Install either within an existing cabinet/cubicle or in a suitable enclosure. If installing two or more protectors together these can be simultaneously mounted and earthed via a CME kit.
Note: allowing for one protector at each end, ESP ThinNet can be installed on segment lengths of up to 148 metres and ESP ThickNet can be used on segment lengths of up to 400 metres.
Suitable accessories
Simultaneously mount and earth up to two ESP ThinNet or ThickNet protectors on a CME 4 or up to four on a CME 8 (see page 43). Enclosures for a single ESP Thick or ThinNet (the WBX 3/G) or for protectors on a CME 4 (the WBX 4) or CME 8 (the WBX 8) can be found on page 44.
Electrical specification
ESP ThinNet | ESP ThickNet | |
Nominal voltage | -2.05V peak | -2.05V peak |
Maximum working voltage | -4.5V peak | -4.5V peak |
Current rating (signal) | 300mA | 300mA |
In-line resistance (± 10%) | 0.5 ohm insert in coax inner | 0.5 ohm insert in coax inner |
Bandwidth (50ohm system) | <0.1dB at 10MHz (<0.3dB at 50MHz) |
<0.1dB at 10MHz (<0.3dB at 50MHz) |
Voltage standing wave ratio | <1.08 | <1.08 |
Transient specification
ESP ThinNet | ESP ThickNet | |
Let through voltage (all conductors)1 5kV,10/700μs test to: BS 6651:1999 Appendix C, Cat C-High ITU (formerly CCITT) IX K17 -signal to screen -signal screen to earth |
20V 325V2 |
20V 325V2 |
Maximum surge current3 | 10kA | 10kA |
1 The maximum transient voltage let-through the protector throughout the test (+/-10%), signal to screen and signal/screen to earth. Response time <10ns.
2 See Ethernet technical note above .
2 Tested with 8/20μs waveshape to ITU (formely CCITT), BS 6651:1999 Appendix C.
Mechanical specification
ESP ThinNet | ESP ThickNet | |
Temperature range | -25°C to +70°C | -25°C to +70°C |
Connection type | Coaxial BNC | Coaxial N type |
Earth connection | M6 stud | M6 stud |
Weight -unit -packaged |
0.2kg 0.23kg |
0.24kg 0.27kg |
Dimensions |
![]() |
Download: