FURSE_Lightning signal devices ESP_ESP 06Q、 ESP 15Q、ESP 30Q、 ESP 50Q、ESP TNQ、ESP RTDQ

Product No:Pro2009414234332
Product Model:ESP 06Q、 ESP 15Q、ESP 30Q、 ESP 50Q、ESP TNQ、ESP RTDQ
UpdateTime:2010.06.02
Views:1590




Protectors for individual data and signal lines are the ESP D series, or ready-boxed to IP66 the ESP D/BX series. Alternatively, for individual protectors with higher current or bandwidth see the ESP E series. For individual 3-wire RTD applications see the ESP RTD
Application
Use these protectors where installation space is at a premium and large numbers of lines require protection. Typically used in process and petrochemical applications to protect supervisory, control and data acquisition systems.
ESP 30Qs mounted on a G DIN rail, protect 48 twisted pair lines.
Features and benefits
Protect four twisted pair lines (plus screens) in one compact unit (ESP 06Q, ESP 15Q, ESP 30Q, ESP 50Q and ESP TNQ).
ESP RTDQ protects three 3-wire lines in RTD applications.
Almost twice as space efficient as smallest competitor .
Standared DIN module (18mm) depth.
Removable (plug-in) terminals allow pre-wiring of cable looms for easier installation.
Built-in DIN rail foot for clip-on mounting to top hat or G DIN rails.
Optional flat mounting on side.
The Q series can be earthed via DIN rail or via the M3 threaded hole in the base (shown here).
2.5mm2 terminals allow for larger cross section wiring, stranded wires terminated with ferrules or fitting two wires into a single terminal.
Low let-through voltage between all line.
Provides repeated protection in lightning intense environments.
Very low resistance to minimise unwanted signal strength reductions.
Strong, flame retardant, ABS housing.
Colour coded terminals (grey for line, green for clean) give a quick and easy installation check.
Screen terminal enables easy connection of cable screen to earth.
Simple, yet substantial, connection to earth via DIN rail.
UK Oftel Approval NS/G/1235/W/100025.
A Q Series protector mounted on a top hat DIN rail. Note the plug-in terminals for easier installation in confined spaces.
Installation
Connect in series with the signal or data line either near where it enters or leaves the building or close to the equipment being protected. Install in a cabinet/cubicle close to the systems earth star point.
ESP 06Q, ESP 15Q, ESP 30Q, ESP50Q or ESP TNQ installed in series.
ESP RTDQ installed in series.
Electrical Specification
ESP 06Q | ESP 15Q | ESP 30Q | ESP 50Q | ESP TNQ | ESP RTDQ | |
Nominal voltage (note 1) |
6V | 15V | 30V | 50V | * | 6V |
Maximum working voltage (note 2) |
7.78V | 18.8V | 37.8V | 57.8V | 190V | 7.78V |
Current rating (signal) | 750mA | 750mA | 750mA | 750mA | 300mA | 700mA |
In-line resistance (per line +/-10%) |
1.0 ohm | 1.0 ohm | 1.0 ohm | 1.0 ohm | 4.3 ohm | 1.0 ohm |
Bandwidth (-3dB 50ohm system) |
1MHz | 2.5MHz | 4MHz | 6MHz | >50MHz | 800kHz |
1 Nominal voltage (DC or AC peak) measured at <5μA (ESP 15Q, ESP 30Q, ESP 50Q) and <200μA (ESP 06Q, ESP RTDQ).
2 Maximum working voltage (DC or AC peak) measured at <5mA leakage (ESP 15Q, ESP 30Q, ESP 50Q)), <10mA (ESP 06Q, ESP RTDQ) and <95μA (ESP TNQ).
Transient Specification
ESP 06Q | ESP 15Q | ESP 30Q | ESP 50Q | ESP TNQ | ESP RTDQ | |
Let-through voltage - all conductors (note 1) 5kV, 10/700μs test to: BS 6651:1999 Appendix C, Cat C-High ITU (formely CCITT) IX K17 |
10.8V | 26.2V | 44.3V | 65.8V | 200V | 10.5V |
Maximum surge current (note 2) per signal wire per pair |
10kA 20kA |
10kA 20kA |
10kA 20kA |
10kA 20kA |
10kA 20kA |
10kA 20kA |
1 The maximum transient voltage let-through the protector throughout the test (+/-10%) line to line and line to earth. Response time <10ns.
2 Pin 1 connected to earth/shell. 3 Tested with 8/20μs waveshape to ITU (formely CCITT), BS 6651:1999 Appendix C.
Mechanical Specification
ESP 06Q | ESP 15Q | ESP 30Q | ESP 50Q | ESP TNQ | ESP RTDQ | |
Temperature range | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C | -25°C to +70°C |
Connection type | Plugable 12 way screw terminal | |||||
Conductor size (stranded) | 2.5mm2 | 2.5mm2 | 2.5mm2 | 2.5mm2 | 2.5mm2 | 2.5mm2 |
Earth connection | Via DIN rail or M5 threaded hole in base of unit | |||||
Dimensions |
Download: